Altronix - T2ZK7F8 - Trove 2V2 8 Door 10Amp Fused
Ideal for a multitude of purposes, including CCTV, Fire Alarm and POIP. A leading global provider of power and transmission technologies for professional security system applications, Altronix develops innovative solutions that integrate disparate infrastructure and maximize overall performance and efficiency.
Altronix Power Supplies are ideal for a multitude of purposes, including:
- General Use
- CCTV
- Fire Alarm
- POIP
eFlow104NB Power Supply/Charger:
Input:
- Voltage: 120VAC, 60Hz, 4.5A max.
- Main Fuse: 6.5A / 250V.
Output:
- Voltage: 24VDC.
- Current: 10A continuous.
- Auxiliary: Class 2 power-limited @ 1A (unswitched).
- Other: Overvoltage protection. Filtered and regulated.
Battery Backup:
- Capacity: 12AH/12VDC (2 within enclosure), 40AH/65AH (requires separate enclosure).
- Type: Sealed lead acid or gel type.
- Fuse Rating: 10A / 32V.
- Failover: Upon AC loss, instantaneous.
Fire Alarm Disconnect:
- Supervised: Latching or non-latching.
- EOL: 10K Resistor.
Supervision:
- AC Failure: Form “C” contacts.
- Battery: Form “C” contacts.
- Low DC Power Shutdown: Shuts down DC output terminals if battery voltage drops below 70-75% for 24V units. Prevents deep battery discharge.
Indicators LED:
- Input: 120VAC is present.
- DC Output: Powered.
PDS8 Dual Input Power Distribution Module:
Input:
- Voltage: 24VDC from eFlow104NB and 12VDC from VR6.
- Main Fuse: 10A / 32V.
Output:
- Voltage: 12 and/or 24VDC.
- Any of the eight (8) power outputs are selectable to follow power Input 1 or Input 2.
- Individual outputs may be set to OFF position for servicing.
- Output Fuses: 3A / 32V.
Indicators LED:
- DC Output: Eight (8) individual output LEDs.
- Green: 12VDC
- Red: 24VDC.
ACM8 Access Power Controller:
Input:
- Voltage: 24VDC from eFlow104NB.
- Main Fuse: 10A / 32V.
Output:
- Voltage: 12VDC.
- Eight (8) 24VDC independently controlled fused outputs:
- a) Fail-Safe and/or Fail-Secure power outputs. Form “C” Relays rated 28VAC or VDC @ 2.5A.
- b) Auxiliary power outputs (unswitched).
- c) Any combination of the above.
- Output Fuses: 3.5A / 32VDC.
Indicators LED:
- Red LEDs: Outputs are triggered (relays energized).
- Blue LED: FACP disconnect is triggered.
VR6 Voltage Regulator:
Input:
- Voltage: 24VDC from eFlow104NB.
Output:
- Voltage: 12VDC.
- Current: 6A continuous.
- Other: Surge suppression.
Indicators LED:
- Input: 24VDC is present.
- Output: Powered.
Environmental:
Temperature:
- Operating: 0° C to 49° C (32° F to 122° F).
- Storage: - 20° C to 70° C ( - 4° F to 158° F).
- Relative Humidity 85% +/- 5%.
- BTU/Hr. (approx.): 128 BTU/Hr.